Product Details:
|
| Test Standard: | GB/T 11785-2005, ISO 9239-1 | Heat Flux Range: | 0 - 15 KW/m2, Accuracy +/-0.2 KW/m2 |
|---|---|---|---|
| Radiant Panel Size: | 300 X 450 Mm, Withstands Approx. 900 C | Radiant Panel Tilt: | 30 Degrees, Adjustable |
| Exhaust Smoke Velocity: | (2.5 +/- 0.2) M/s | Flame Height: | 60 - 120 Mm Adjustable |
| Fuel Gas: | Propane, (0.026 +/- 0.002) L/s | Power Supply: | AC 220V +/-10%, 50Hz, 5kW Max |
| Burning Chamber Size: | 1420 X 1200 X 2300 Mm | Equipment Weight: | 350 Kg |
| Control Mode: | Computer Control With Automatic Timing And Report Printing | ||
| Highlight: | Radiant Heat Flux Test Apparatus,ISO 9239-1 Radiant Panel Tester,Flooring Materials Flammability Tester |
||
Overview
The DX8401 radiant heat flux test apparatus evaluates the burning behaviour of horizontally mounted flooring materials that are ignited by a small pilot flame and exposed to an inclined radiant heat field. It reproduces the radiant heat source method specified in GB/T 11785-2005 and ISO 9239-1, so laboratories can compare flame spread, critical heat flux and smoke development of floor coverings under controlled conditions. Test results reflect the complete flooring system, including backing material, subfloor and coating layers.
Applications
Compliant Standards
GB/T 11785-2005 and ISO 9239-1 — Reaction to fire tests for floorings, determination of the burning behaviour using a radiant heat source.
Technical Parameters
| Heat flux meter range | 0 – 15 kW/m² |
| Heat flux meter accuracy | ±0.2 kW/m² |
| Heat flux meter precision | better than ±3% |
| Radiant high temperature meter | 400 – 600 °C, accuracy ±0.5 °C |
| Black body temperature deviation | ±5 °C |
| Exhaust smoke velocity | (2.5 ±0.2) m/s |
| Exhaust capacity | 39 – 85 m³/min |
| Porous refractory radiant panel | 300 mm × 450 mm, withstands approx. 900 °C |
| Thermocouple | 3.2 mm K type stainless steel sheathed |
| Heat flux distribution | 200 mm: (9.1 ±0.4) kW/m²; 400 mm: (5.0 ±0.4) kW/m²; 600 mm: (2.4 ±0.2) kW/m² |
| Fuel gas | Propane (supplied by user), flow rate (0.026 ±0.002) L/s |
| Pilot burner | Outer diameter 10 mm, inner diameter 6 mm, 35 holes of 0.7 mm on the tube |
| Flame height | 60 – 120 mm, adjustable |
| Ignition system | High voltage electronic ignition |
| Radiant panel tilt | 30 degrees, adjustable |
| Chamber material | 1.2 mm 304 stainless steel, CNC formed with rounded profile |
| Power supply | AC 220 V ±10%, 50 Hz, maximum 5 kW |
| Burning chamber size | L1420 × W1200 × H2300 mm |
| Control cabinet size | 2200 × 1200 × 2400 mm |
| Equipment weight | 350 kg |
| Timing accuracy | better than 1 s/h |
System Configuration
Features
Scope of Supply and Service
Each unit is assembled, wired and calibrated before shipment, then packed in an export wooden case. Commissioning guidance, operation manual and spare part support are provided. OEM labelling and on site installation service are available on request.
![]()
Contact Person: Sophia Su
Tel: +86-13266221899