DX9027 Fire Extinguisher Vibration Tester
Conform to the standard: meet the design requirements of 7.1.4 spray performance test after the collision of the fire extinguisher in GB/T 4351.1-2005 "Performance and Structural Requirements for Portable Fire Extinguishers Part 1".
Scope of application: Mainly suitable for vibration test of 1kg~8kg portable fire extinguisher.
Test method: After weighing the dry powder fire extinguisher, place it in a 20℃±5℃ environmental constant temperature room for 18h or more and then take it out, fix the fire extinguisher on the instrument in an upright state, and fall freely from a height of 15mm to a thick steel plate placed horizontally at a frequency of 1Hz.
Technical Parameters:
Collision frequency: 1Hz (1 time/sec)
Vibration height: 0-15mm (adjustable)
Number of vibrations: 0-1000 times adjustable; It will automatically stop when the set number of times is reached.
Impact baseplate: thickness 60mm±1mm, length 300mm±5mm, width 300mm±5mm
Maximum load: maximum load 50kg
Inlet pressure: 0.1~0.2 Mpa
Workstation: 1 station
Power supply: 220V, 50HZ, 0.5kw
Machine size: about 750×500×1300